HEYLast revision: 11/20/2020
Our HMI SCADA YouTube channel contains instructional and promotional videos on our various product lines. Please follow the links below:
Platform Connectivity and Device Integration Playlist
https://www.youtube.com/playlist?list=PLJq4rR8tWINwTpCnlHqjUUlysBClU-YqU
HMI SCADA Channel Main Page
https://www.youtube.com/user/wonderwarehmi
You can now access hundreds of training courses that cover simple and complex topics with all the products that you use in our Monitoring and Control portfolio. Access to the eLearning modules is free!
https://sw.aveva.com/training/wonderware
This document contains important information about ABCIP Communication Driver. Review this document for known issues and changes to the ABCIP Communication Driver.
Installation
The ABCIP Communication Driver is installed along with the Communication Drivers Pack. It is a selectable option during the Communication Drivers Pack installation.
The ABCIP Communication Driver will always be compatible with the latest release of System Platform. For a detailed information on product and platform compatibility, refer to the Technology Matrix section of the Global Customer Support (GCS) Site.
For a list of supported operating systems for the communication drivers, refer to the Technology Matrix, available at the Global Customer Support (GCS) Site:
The Technology Matrix is a searchable database that contains the latest product information. Enter the product name in the search bar, then select the release to view:
To run a Communication Driver, the following hardware configurations are the minimum recommended:
Please reference the Online Compatibility Matrix for the latest list of controllers and supported firmware. Additional information is available from the AVEVA Global Customer Support (GCS) Compatibility Matrix, and in the ABCIP Communication Driver help.
To support the Auto-Build feature:
The following issues are resolved in this release.
Defect ID |
SR/Case Number |
Description |
CR-L00156234 CR-L00155914 |
SR-63511595 |
All data was gradually returned after 30 minutes when the communication was lost. |
CR-L00155251 |
SR-75110225 |
DEMAND READ and DEMAND WRITE Timing out when one of the PLCs was shutdown. |
CR-L00154060 |
SR-31613884 |
ABCIP was not running after starting multiple instances at the same time. |
CR-L00151244 |
SR-54810623 |
ABCIP process consumption of CPU and memory steadily increased to point of non function of server over 1-2 weeks. |
CR-L00149502 |
SR-44311716 SR-37115204 |
Memory leak when connecting to a faulted PLC (or a PLC with no Program). |
CR-L00148999 |
SR-223110242 |
Writing one bit to true in an int or dint array element can cause several bits to get set to true if you also write an integer value to a different element in the same array in the same transaction. |
CR-L00145700 |
SR-103145265 |
Couldnot connect to a CompactLogix 5069-L320ER - Firmware 28. The tag database upload failed with errors: STS=0101, ExtSTS=0312: Link Address specified in Port Segment Not Available. |
CR-L00145360 CR-L00144113 CR-L00146111 |
SR-54810279 SR-54810279 SR-54810325 SR-45210260 |
OI-ABCIP did not reconnect automatically after PLC was powered off or disconnected from network. |
CR-L00145245 |
SR-14414165 |
Some of the boolean tags were not showing the correct values when compared to RSLinx. Also STS=1E errors that caused bad quality items and possibly caused the PLC to major fault and lose its program. |
CR-L00149163 CR-L00149608 |
SR-48912116 |
DAS ABCIP hanged after running for a while. |
IMS-575825 |
IMS-960009443 |
A note was missing in the new ABCIP Communication Driver Help for Max CIP Connections, which was there in the older versions of the DAS ABCIP Help. |
There are no known issues in this release.
The ABCIP Communication Driver documentation set includes the following guides:
Note: The AVEVA Enterprise License Manager Help can be accessed through the License Manager application (available only for the new license framework). For earlier versions of the license framework, see License Utility Guide.
© 2020 AVEVA Group plc and its subsidiaries. All rights reserved. | Contact Us |